RSI Water condition Action
4.0<RSI<5.5 High boiler scale formation Regular inspection and descaling operation
necessary.
5.6<RSI<6.2 Slight boiler scale formation Water treatment not necessary.
Occasional inspection recommended.
6.3<RSI<6.8 Neutral water Water treatment not necessary.
Occasional inspection recommended.
6.9<RSI<7.5 Slight corrosion at higher
temperature
Water treatment not necessary.
Occasional inspection recommended.
7.6<RSI<9.0 Strong corrosion Regular inspection necessary, use of corrosion
inhibitor recommended.
9.1<RSI<11 Very strong corrosion Regular inspection necessary, use of corrosion
inhibitor required.
RSI>11 Very strong corrosion in
complete water system
Water should not be used.
The table indicates that distilled or demineralized water should never be used, as their RSI is > 11.
The RSI only indicates the equilibrium of scaling - descaling. A cooling water showing good RSI
conditions can still be unsuitable due to other factors.
From the table above, the RSI index should be between 5.6 and 7.5; if not, consult your local Atlas Copco
Customer Centre.
pH
The effect of pH is already calculated in the Ryznar index, but the pH itself has some additional
limitations : 6.8 < pH < 8.5
Total Dissolved Solids (TDS)
This is the sum of all the ions in the water. It can be derived from the dry residue after evaporation (but not
including suspended solids), or it can be estimated from the electrical conductivity.
In a closed system, the following limits apply : TDS < 3000 mg/l (< 3800 microS/cm)
For an open system, the following limits apply : TDS < 750 mg/l ( < 960 microS/cm)
Chlorides (Cl
-
)
Chloride ions will create pitting corrosion on stainless steel. Their concentration should be limited:
Closed cooling system : chlorides < 500 ppm
Open cooling system : chlorides < 150 ppm
However, if the water is scaling, lower limits should be used. (See The Ryznar stability index (RSI)).
Free chlorine (Cl
2
)
A level of 0.5 ppm should not be exceeded for long periods.
For shock treatments, a maximum limit of 2 ppm for maximum 30 minutes/day applies.
Instruction book
2920 1815 04 233

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Atlas Copco ZR 110 and is the answer not in the manual?

Atlas Copco ZR 110 Specifications

General IconGeneral
BrandAtlas Copco
ModelZR 110
CategoryAir Compressor
LanguageEnglish

Related product manuals