Top up, if necessary, with the correct type of oil.
Adjustment of mix-air (for ZR/ZT 110 up to ZR/ZT 145 Full-Feature compressors)
Only for 13 bar (190 psi) Full-Feature compressors or 10 bar (145 psi) and 10.4 bar (150
psi) Full-Feature compressors designed for an ambient temperature of up to 50 ˚C (122 ˚F)
If, due to changes of the ambient temperature, the Elektronikon regulator shows a warning
for the regeneration air temperature, the mix-air must be readjusted.
On most ZT compressors, the shut-off valve (1) is located in the cooler compartment and
the regulating valve (2) is located in the compressor compartment. The safety grating must
be fitted again and the door of the cooler compartment must be closed before starting the
compressor.
The operator must wear heat-resistant gloves and shirts with long sleeves before executing
below adjustments.
Mix-air regulation valves, ZR compressors
Instruction book
250 2920 1815 04