ATTACK EKO - Setting Modulation Electronics (ATTACK EZ); Trimmer Adjustments; Jumper Settings

ATTACK EKO
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
| 17
CAST IRON FLOOR STANDING GAS BOILER
advice from the instructions you can use all the advantages of the boiler and avoid various failures
and claims.
You will be awarded by comfortable moments and satisfied with your investment.
Classification of the appliance by STN 070240
Appliance category: I
2
H
Boiler design: B11BS
Connection overpressure of natural gas G20: 20 mbar
SETTING OF THE MODULATION ELECTRONICS OF THE ATTACK EZ BOILER
1. Trimmers
P1 – CH. CAPACITY – setting of the max.
boiler output into the heating system
P2 – ING. CAPACITY – setting of the start-
ing output (10 seconds after ignition)
2. Jumpers
JP1 – natural gas – connected
JP2 – anti-cycling timer
1 – 60 seconds
2 – 120 seconds
3 – 180 seconds
JP3 – connected (should not be
disconnected)