General data of the Profinet interface
CC-B (Conformance Class B) for the Profinet application of the AC actuator controls
CC-C (Conformance Class C) for the integral switch function
Conformance class
IIINetload Class
Via TCP/IP and integral web server possibleDevice diagnostics via Ethernet
Via GSD (ml) file (available for download at www.auma.com)Device integration
Commands and signals of the Profinet interface
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable local
controls, Interlock OPEN/CLOSE, PVST
Process representation output
(command signals)
End positions OPEN, CLOSED
Actual position value
Actual torque value, requires MWG in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Process representation input
(feedback signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
Process representation input
(fault signals)
The behaviour of the actuator is programmable:
Stop in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
Execute last received operation command
Behaviour on loss of communication
43
Actuator controls
AC 01.2/ACExC 01.2 Profinet Technical data