1. Refer to table and check if swing angle corresponds to the setting of the reduc-
tion gearing (stages 1– 9).
Table 27:
Actuator swing angle and suitable reduction gearing setting
SQ 14.2SQ 12.2SQ 10.2SQ 05.2 / SQ 07.2
432230° +/–15°
543360° +/–15°
643390° +/–15°
6543120° +/–15°
6544150° +/–15°
7544180° +/–15°
7654210° +/–15°
7655290° +/–70°
2. To modify settings, lift the lever at the reduction gearing and engage at the se-
lected stage.
Figure 85: Set reduction gearing
11.3. Mechanical position indication via indicator mark (not self-adjusting)
Figure 86: Mechanical position indication via indicator mark
The mechanical position indicator shows the valve position via two indicator discs
with symbols (OPEN) and (CLOSED). When correctly set, the symbols
OPEN/CLOSED point to the indicator mark at the cover in the end positions.
Setting elements
The position indications is housed in the actuator switch compartment. The switch
compartment must be opened to perform any settings. Refer to <Switch compartment:
open/close>.
75
SQEx 05.2 – SQEx 14.2/SQREx 05.2 – SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP Commissioning (settings in the actuator)