3. Turn potentiometer [1] clockwise to the stop.
4. Turn potentiometer [1] slightly in opposite direction.
5. Turn potentiometer [2] clockwise until output current starts to increase.
6. Turn potentiometer [2] in opposite direction until the following value is reached:
- for 0 20 mA approx. 0.1 mA
- for 4 20 mA approx. 4.1 mA
This ensures that the signal remains above the dead and live zero point.
7. Move valve to end position OPEN.
8. Set potentiometer [3] to end value 20 mA.
9. Approach end position CLOSED again and check minimum value (0.1 mA or
4.1 mA). If necessary, correct the setting.
64
SQ 05.2 SQ 14.2 / SQR 05.2 SQR 14.2 Control unit - electromechanical
Commissioning (optional equipment settings) AC 01.2 Intrusive Modbus RTU