installation and operation manual
2016-08-26 23
Error type
Display
message
Error
code
Error description Action
Over
voltage
OV-G-V
1010
Grid voltage exceeds the
standard set in the inverter
1. Wait to see if the grid voltage returns within limits.
2. If problem persists, check whether the grid standard is set correctly in Advanced
Settings (see 6.6).
3. Check V_AC, grid voltage, in Information display of inverter (see 6.3) and
perform independent measurement of grid voltage to confirm that the inverter
reading is correct. If the measured voltage is outside the local grid standard
limits, please contact your local utility as it may require monitoring and
adjustment
4. With agreement from utility it is possible to set a user defined voltage range (see
6.6).
Under
voltage
UN-G-V
1011
Grid voltage is below the
standard set in the inverter
Over
frequency
OV-G-F
1012
Grid frequency exceeds the
standard set in the inverter.
1. Wait to see if the grid frequency returns within limits.
2. If a problem persists, check whether the grid standard is set correct in Advanced
Settings (see 6.6).
3. Check grid frequency, in Information display of inverter (see 6.3) and perform
independent measurement of grid frequency to confirm that the inverter
reading is correct. If the measured frequency is outside the local grid standard
limits, please contact your local utility as it may require monitoring and
adjustment.
4. With agreement from utility it is possible to set a user defined frequency range
(see 6.6).
Under
frequency
UN-G-V
1013
Grid frequency is below the
standard set in the inverter.
Grid
impedance
G-IMP
1014
High grid impedance
1. Wait to see if the grid returns within limits.
2. If problem persists please contact your local utility as it may require monitoring
and adjustment.
No Grid
NO Grid
1015
The inverter cannot detect a
grid.
1. Check your AC power connections and switches.
2. Restart the inverter.
3. Call your local grid to resolve the black out.
10.3 Grid errors