Digital Counter / Timer / Tach User Manual, 1st Ed.
1-800-633-0405
4-58
Timer + Counter Mixed Mode
In Timer + Counter Mixed Mode, timer period setting value SV1 controls Output 1 and counter setting value SV2
controls Output 2. Output 1(Timer) will turn ON momentarily for the time set in the output pulse width parameter
(
tout1
) or will be maintained ON (
tout1
set to 0.00). Output 2 (Counter) will turn ON momentarily for the
time set in the output pulse width parameter (
tout2
) or will be maintained ON depending on the output mode
selected.
CTT Timer + Counter Mixed Mode Functions
Timer Mode - Power On Delay HOLD (PondH)
Counter Input Mode -Down (
down
)
Timer Mode - Power On Delay HOLD (
PondH
)
When power is applied to the CTT, the timing period setting value SV1
will begin timing up or down based on parameter (
t modE
). At the end
of the timing period Output 1 will turn ON momentarily for the time set
in the output pulse width parameter (
tout1
) or will be maintained ON
if the output pulse width parameter (
tout1
) is set to 0.00.
The leading edge of a “reset” input signal at RST1 will turn OFF Output
1, reset the timing period and prohibit the start of a new timing period.
The “reset” signal minimum pulse width is set by reset pulse width param-
eter (
rtSr
).
The leading edge of an “pause” input signal at GATE will pause the
timing period after it has been started. The timing period will continue
after the trailing edge of the “pause” (Gate) signal.
When power is removed, Output 1 will turn OFF. The last state of the
output and the last value of the current timing period will be “stored”
when power is removed. When power is reapplied the output will return
to its last state and timing will resume from the last value of the timing
period.
Counter Input Mode:
Mode F (
F
)
When the count present value PV counts down to 0, Output 2
will turn ON. The count PV will continue to decrement with
each input signal.
The leading edge of a “reset” input signal at RST1 will turn
Output 2 OFF, reset the count PV to the count setting value
SV2, and prohibit an input signal from decrementing the count
PV. The trailing edge of the “reset” signal at RST1 enables
counting to begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
).
Counter Output Modes:
Counter Input Mode - Counting Down (
down
)
Each leading edge of the input signal at CP1 will decrement the count present value PV by 1.
Timer+Counter Mixed Mode
OUT2
TIMER + COUNTER
C
ounter Input Mode DOWN
Counter Output Mode F
999999
RESET
COUNT SV
2
COUNT PV
0
Power signal
Start signal
Pause signal
Reset
Output
signal
Up
Down
SV
SV
0
0
Power On Delay Hold
tt t