Chapter 3: Keypad Operation and Setup Parameters
SOLO Basic Temperature Controller User Manual
3–8
o1-s
/ o2-s
Output 1 / Output 2 Hysteresis
Range: 0.0 to 999.9
The Output Hysteresis parameter defines the amount that the PV must
go below or above the SV before the output turns on. This parameter
is available only for On / Off control and hysteresis direction will be
dependent on whether the output is set for heating or cooling.
PV
ON
OFF
Output
PV
ON
OFF
Output
o1-h
/ o2-h
Output 1 / Output 2 Heating Period
Range: 0.1 to 60 seconds
The Output Heating parameter defines one output period or the
duration of one on / off cycle for the Output.
Output Heating Period
This parameter is available when the Output is programmed as a
heating output. Available in PID and Manual mode.
o1-C
/ o2-C
Output 1 / Output 2 Cooling Period
Range: 0.1 to 60 seconds
The Output Cooling parameter defines one output period or the
duration of one on / off cycle for the Output.
Output Cooling Period
This parameter is available when the Output is programmed as a
cooling output. Available in PID and Manual mode.