Chapter 3: Keypad Operation and Setup Parameters
SOLO Basic Temperature Controller User Manual
3–8
o1-s
/ o2-s
Output 1 / Output 2 Hysteresis
Range: 0.0 to 999.9
The Output Hysteresis parameter defines the amount that the PV must
go below or above the SV before the output turns on. This parameter
is available only for On / Off control and hysteresis direction will be
dependent on whether the output is set for heating or cooling.
Heating Hysteresis
PV
SV
ON
OFF
Output
Cooling Hysteresis
PV
SV
ON
OFF
Output
o1-h
/ o2-h
Output 1 / Output 2 Heating Period
Range: 0.1 to 60 seconds
The Output Heating parameter defines one output period or the
duration of one on / off cycle for the Output.
Output Heating Period
This parameter is available when the Output is programmed as a
heating output. Available in PID and Manual mode.
o1-C
/ o2-C
Output 1 / Output 2 Cooling Period
Range: 0.1 to 60 seconds
The Output Cooling parameter defines one output period or the
duration of one on / off cycle for the Output.
Output Cooling Period
This parameter is available when the Output is programmed as a
cooling output. Available in PID and Manual mode.