Chapter 3: Keypad Operation and Setup Parameters
SOLO Basic Temperature Controller User Manual
3–10
Operation Mode Parameters
Press the
button to access these parameters.
r-s
Run / Stop
The Run / Stop parameter is used to control the operational status of
the SOLO Basic Controller. The controller can either be in run mode
or stop mode. During stop mode the output is turned off but alarms
remain active.
run
Run mode
stop
Stop mode
sp
Decimal Point Position
Range: 0 (****)
1 (***.*) Note: Maximum temperature displayed (PV) will be
limited to "999.9".
This parameter defines the decimal point position on the PV and SV
display.
loC
Lock Mode
Range:
off
The Lock feature is disabled.
loC1
Lock Mode 1
LoC2
Lock Mode 2
Lock Mode 1: All key pad operation is ignored.
Lock Mode 2: All key pad operation is ignored except changing the
SV. To unlock press the
;
key and the
'
key at the same time to
display KEYP parameter. Enter the password to unlock the key. Default
password is 0000.
al1h
Alarm 1 High Limit
This parameter is used to set the high limit for Alarm 1. The range and
availability are dependent on the selected alarm mode.
al1l
Alarm 1 Low Limit
This parameter is used to set the low limit for Alarm 1. The range and
availability are dependent on the selected alarm mode.
al2h
Alarm 2 High Limit
This parameter is used to set the high limit for Alarm 2. The range and
availability are dependent on the selected alarm mode.
al2l
Alarm 2 Low Limit
This parameter is used to set the low limit for Alarm 2. The range and
availability are dependent on the selected alarm mode.