SOLO Basic Temperature Controller User Manual
3–11
Chapter 3: Keypad Operation and Setup Parameters
1st Ed. 01/19
out1
/ out2
Output 1 / Output 2 Level
Range: 0.0 to 100 (%)
The value for this parameter can be changed in the Manual control
mode. In other control modes, this parameter is read-only.
o1mA
/ o2ma
Output 1 / Output 2 Upper Limit
Upper output percentage. Linear calculation is done between the
upper and lower limit. Range of 0.0 to 100 with a system default of
100.
o1mi
/ o2mi
Output 1 / Output 2 Lower Limit
Lower output percentage. Linear calculation is done between the lower
and upper limit. Range of 0.0 to 100 with a system default of 0.0.