Chapter 4: AC Drive Parameters
4–58
Auto Restart after Fault Default Setting: 00
Range: 00 to 10
After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC
drive can be reset/restarted automatically up to 10 times. Setting this parameter to
0 will disable the reset/restart operation after any fault has occurred. When
enabled, the AC drive will restart with speed search, which starts at the previous
Frequency. To set the fault recovery time after a fault, please see (P6.13) base-
block time for speed search.
Momentary Power Loss Default Setting: 00
Settings:
00 Stop operation after momentary power loss.
01 Continue operation after momentary power loss; speed search from
Speed Reference.
02 Continue operation after momentary power loss; speed search from
Minimum Speed.
Reverse Operation Inhibit Default Setting: 00
Settings:
00 Enable Reverse Operation
01 Disable Reverse Operation
This parameter determines whether the AC Motor Drive can operate in the reverse
direction.
P6.03
This parameter will only work if the Source of Operation (P3.00) is set to something
other than 00 (Operation determined by digital keypad).
P6.02
P6.01
DURAPULSE AC Drive User Manual