5–21
Configure the DirectLOGIC CPUs
DirectLOGIC MODBUS Port Configuration for D2-260 and DL06
The following configuration example is specific to the D2-260 and DL06. Refer to
the appropriate CPU User Manual for the specifics on your DirectLOGIC CPU.
• In DirectSOFT, choose the PLC menu, then Setup, then ”Secondary Comm Port”.
• From the Port number list box at the top, choose “Port 2”.
• For the Protocol, select “MODBUS”.
• Response Delay Time should be “0ms”. Both RTS on and off delay times must be
set to 0ms .
• The Station Number should be set to “1” to make the D2-260 or DL06 CPU a
MODBUS master.
• The Baud Rate should be set at “9600” (or higher, if using an FA-ISOCON network
adapter module).
• In the Stop Bits list box, Choose “1”.
• In the Parity list box, choose “Odd”.
Chapter 5: DURAPULSE MODBUS Communications
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013