4â15
Detailed Parameter Listings
Motor Parameters
Motor Nameplate Voltage Default Setting: 230V class - 240 / 460V class - 480
Settings: 230V series: 200/208/220/230/240
460V series: 380/400/415/440/460/480
This parameter determines the Maximum Output Voltage of the AC drive. The
Maximum Output Voltage setting must be less than or equal to the rated voltage of
the motor as indicated on the motor nameplate. The setting value must be equal
to or greater than the Mid-Point Voltage (P2.05).
Motor Nameplate Amps Default Setting: Drive Rating (A)
Range: Drive Rated Amps x 0.4 to Drive Rated Amps x 1.0
This parameter sets the output current to the motor, and is used by the drive to set
the motor overload protection. Set this parameter value to the full load current
listed on the motor nameplate. (Also refer to P6.00 to set overload current type.)
Motor Base Frequency Default Setting 60
Range: 50/60/400
This parameter should be set to the base frequency of the motor as indicated on
the motor nameplate. Motor Base Frequency determines the volts per hertz ratio.
P0.02
P0.01
P0.00
If the
î
symbol is found next to the parameter name, the parameter can be edited
when the AC drive is in RUN Mode.
Motor Nameplate Voltage Default Setting: 230V class - 240; 460V class - 480
Settings: 230V series: 200/208/220/230/240
460V series: 380/400/415/440/460/480
This parameter determines the Maximum Output Voltage of the AC drive. The Maximum
Output Voltage setting must be less than or equal to the rated voltage of the motor as
indicated on the motor nameplate. The setting value must be equal to or greater than the
Mid-Point Voltage (P2.05).
P0.00
Parameter
Number
Parameter Setting
Range
Parameter
Description
Parameter Default
Setting
Parameter
Name
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013