Chapter 3: Keypad Operation and Quickstart
3–18
Write Parameter Settings to Drive
After the COPY KEYPAD parameter is enabled, the LCD display will show an
additional group called COPY KEYPD GROUP. Press the PROGRAM key and
then the UP/DOWN or PROGRAM keys until this new group is displayed.
Press the ENTER key to display the copy mode selections.
Select the WRITE TO DRIVE mode using the UP/DOWN keys.
Press the ENTER key to display the four (4) available program numbers to write
from the keypad to the AC drive. The program name must match the part number
of the AC drive being programmed; for example: GS3-2025.
Use the UP/DOWN keys to select the desired program number; PGM1 thru
PGM4 and press the ENTER key.
Use the UP/DOWN keys to select “Yes” to confirm and press the ENTER key.
The LCD display will show the message “Keypad => Drive, Loading...” while the
parameters are being copied and return to the program selection when finished.
Loading...
servicing.
WARNING: Do not remove the Keypad during transfer of program parameter settings
to or from the AC drive.
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013