Digital Parameters
Source of Operation Command Default Setting: 00
Settings:
00 Operation Determined by Digital Keypad
01 Operation determined by external control terminals.
Keypad STOP is enabled.
02 Operation determined by external control terminals.
Keypad STOP is disabled.
03 Operation determined by communication interface.
Keypad STOP is enabled.
04 Operation determined by communication interface.
Keypad STOP is disabled.
This parameter sets the input source for the AC drive operation commands. Refer
to P3.01 to P3.10 for more details.
Multi-Function Input Terminals (DI1-DI2) Default Setting: 00
Settings:
00 DI1 - FWD/STOP
DI2 - REV/STOP
01 DI1 - RUN/STOP
DI2 - REV/FWD
02 DI1 - RUN (used with momentary N.O. contact)
DI2 - REV/FWD
DI3 - STOP (used with momentary N.C. contact)
REV/STOP
FWD/STOP
DCM
DI2
DI1
DI1
DI2
Result
OFF
OFF
STOP
ON
OFF
FWD
OFF
ON
REV
ON
ON
STOP
P3.01: Setting 00
DI1- RUN/STOP select
"Open" : Stop
"Close" : Run
DI2- FWD/REV select
"Open" : FWD
"Close" : REV
FWD/REV
RUN/STOP
DCM
DI2
DI1
P3.01: Setting 01
DI1- RUN command
Latching input (N.O.)
Runs from momentary
contact closure
DI3- STOP command
Latching input (N.C.)
Stops from momentary
contact opening
DI2
DI3
DI1
DCM
STOP
RUN
FWD/REV
DI2- FWD/REV select
"Open" : FWD
"Close" : REV
P3.01: Setting 02
Multi-function Input Terminals DI1 and DI2 do not have separate parameter
designations. DI1 and DI2 must be used in conjunction with each other to operate
two and three wire control.
P3.01
P3.00
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013