Chapter 4: AC Drive Parameters
4–30
Multi-Function Input (DI3) Default Setting: 00
Multi-Function Input (DI4) Default Setting: 03
Multi-Function Input (DI5) Default Setting: 04
Multi-Function Input (DI6) Default Setting: 05
Multi-Function Input (DI7) Default Setting: 06
Multi-Function Input (DI8) Default Setting: 09
Multi-Function Input (DI9) Default Setting: 02
Multi-Function Input (DI10) Default Setting: 12
Multi-Function Input (DI11) Default Setting: 10
Settings for P3.02 to P3.10:
00 **External Fault (N.O.)
01 **External Fault (N.C.)
02 External Reset
03 Multi-Speed Bit 1 / PID Setpoint Bit 1
04 Multi-Speed Bit 2 / PID Setpoint Bit 2
05 Multi-Speed Bit 3 / PID Setpoint Bit 3
06 Multi-Speed Bit 4
07 Manual Keypad Control
08 Reserved
09 Jog
10 External Base Block (N.O.)
11 External Base Block (N.C.)
12 Second Accel/Decel Time
13 Speed Hold (P4.00 must be set to 01.)
14 ***Increase Speed (P4.00 must be set to 01.)
15 ***Decrease Speed (P4.00 must be set to 01.)
16 Reset Speed to Zero (P4.00 must be set to 01.)
17 PID Disable (N.O.)
18 PID Disable (N.C.)
*19 1st/2nd Source Select (N.O.)
*20 1st/2nd Source Select (N.C.)
99 Input Disable
* Parameter setting available only with firmware v1.04 or higher (refer to P9.39)
** Use either setting 00 or 01, but not both. Use interposing relays if more contacts
are needed.
*** Accel / Decel times must be more than one second in order for Increase (14)
and Decrease (15) Speed settings to work efficiently.
P3.10
P3.09
P3.08
P3.07
P3.06
P3.05
P3.04
P3.03
P3.02
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013