Chapter 4: AC Drive Parameters
4–60
Auto Adjustable Accel/Decel Default Setting: 00
Settings:
00 Linear Accel/Decel
01 Auto Accel, Linear Decel
02 Linear Accel, Auto Decel
03 Auto Accel/Decel
04 Auto Accel/Decel Stall Prevention
If the auto accel/decel is selected, the AC drive will accel/decel in the fastest and
smoothest means possible by automatically adjusting the time of accel/decel.
This parameter provides five modes to choose:
• 00 Linear Acceleration and deceleration (operation by P1.01,
P1.02 or P1.05, P1.06 acceleration/deceleration time).
• 01 Automatic acceleration, linear deceleration (Operation by automatic
acceleration time, P1.02 or P1.06 deceleration time).
• 02 Linear acceleration and automatic deceleration (Operation by automatic
acceleration time, P1.01 or P1.05 acceleration time).
• 03 Automatic acceleration, deceleration (Operation by AC drive auto adjustable
control).
• 04 Auto acceleration, deceleration. The auto accel/decel will not be quicker than
the settings for acceleration (P1.01 or P1.05) or deceleration (P1.02 or P1.06).
The operation is specific to preventing a stall.
Over-Torque Detection Mode Default Setting: 00
Settings:
00 Disabled
01 Enabled during constant speed operation
02 Enabled during acceleration
Over-Torque Detection Level Default Setting: 150
Range: 30 to 200%
• A setting of 100% is proportional to the Rated Output Current of the drive.
• This parameter sets the Over-Torque Detection level in 1% increments. (The AC
drive rated current is equal to 100%.)
Over-Torque Detection Time Default Setting: 0.1
Range: 0.1 to 10.0
This parameter sets the Over-Torque Detection Time in units of 0.1 seconds.
P6.09
P6.08
P6.07
P6.06
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013