PV 100% Value Default Setting: 100.0
Range: 0.0 to 999
This parameter should be set to the value corresponding to the 100% value of the
process variable (PV). The setting for P7.01 cannot be less than any setting for
P7.10 to P7.17.
PID Setpoint Source Default Setting: 02
Settings:
00 Keypad
01 Serial Communications*
02 AI1 (0 to 10V)
03 AI2 (4 to 20mA)
The user may change the display to PID setpoint by changing P8.00 to 07 on the
keypad.
PID Feedback Gain
Default: 100
Range: 00 to 300.0%
PID Setpoint Offset Polarity
Default: 00
Settings:
00 No Offset
01 Positive Offset
02 Negative Offset
This parameter functions similarly to P4.01, Analog Input Offset Polarity.
• This parameter only affects analog inputs AI1 and AI2. It does not affect AI3.
PID Setpoint Offset
Default: 0.0
Range: 0.0 to 100.0%
This parameter functions similarly to P4.02, Analog Input Offset.
• This parameter only affects analog inputs AI1 and AI2. It does not affect AI3.
PID Setpoint Gain
Default: 100
Range: 0.0 to 300.0%
This parameter functions similarly to P4.03, Analog Input Gain.
• This parameter only affects analog inputs AI1 and AI2. It does not affect AI3.
P7.06
P7.05
P7.04
P7.03
* Serial communication PID setpoint uses P7.10 memory address:
Hexadecimal - 070A, MODBUS Decimal - 41803, Octal - V3412.
P7.02
The setting for PV 100% value (P7.01) cannot be set less than any value set for P7.10
to P7.17. If you are unable to reduce P7.01 to the desired value, check parameters
P7.10 to P7.17, and reduce these values accordingly.
P7.01
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual