Chapter 4: AC Drive Parameters
4–76
Serial Comm Speed Reference
Default Setting: 60.0
Range: 0.0 to 400.0 Hz [16-bit binary (HEX) format]
This parameter is used to set the Frequency Command when the AC drive is
controlled by communication interface.
Serial Comm RUN Command
Default Setting: 00
Settings:
00 Stop
01 Run
• Do not write both RUN (P9.27) & JOG (P9.31) Commands in the same write
instruction. Use separate write instructions from the master computer or PLC.
Serial Comm Direction Command
Default Setting: 00
Settings:
00 Forward
01 Reverse
Serial Comm External Fault
Default Setting: 00
Settings:
00 No action
01 External fault
Serial Comm Fault Reset
Default Setting: 00
Settings:
00 No action
01 Fault Reset
Serial Comm JOG Command
Default Setting: 00
Settings:
00 Stop
01 Jog
• Do not write both RUN (P9.27) & JOG (P9.31) Commands in the same write
instruction. Use separate write instructions from the master computer or PLC.
Firmware Version Default Setting: ##
Settings: Factory Set, Read Only
• This parameter is available only with AC drive firmware v1.02 or higher.
P9.39
P9.31
P9.30
P9.29
P9.28
In order for this parameter to function, the Source of Operation Command (P3.00)
must be set to 03 or 04.
P9.27
In order for this parameter to function, the Source of Frequency Command (P4.00)
must be set to 05.
P9.26
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013