Chapter 1: Getting Started
1–8
Please review the AutomationDirect Terms and Conditions for this product.
There is no 30-day money-back guarantee on any drive over 10 hp.
460V Class – Three Phase (continued)
Model Name: GS3-xxx 4020 4025 4030 4040 4050 4060 4075 4100
Output
Rating
Maximum Motor Output
HP
20 25 30 40 50 60 75 100
kW
15 18.5 22 30 37 45 55 75
Rated Output Current (A)
32 38 45 60 73 91 110 150
Maximum Output Voltage
Three-phase 380 to 480V (proportional to input voltage)
Rated frequency
0.1 to 400 Hz
* Input
Rating
Rated Voltage/Frequency
Three-phase,
380/400/415/440/460/480; 50/60 Hz
Rated Input Current (A)
32 39 49 60 63 90 130 160
Voltage/Frequency Tolerance
Voltage: ± 10% Frequency: ± 5%
Short Circuit Withstand
(SCCR) (A, rms symmetrical)
5kA @ 480 VAC 10 kA @ 480 VAC
Watt Loss 100% I (W)
620 788 1290 1420 1680 2020 2910 3840
Weight (lb [kg])
26.5
[12]
26.5
[12]
26.5
[12]
77.2
[35]
77.2
[35]
77.2
[35]
116.8
[53]
116.8
[53]
* All 3-phase power sources must be symmetrical. Do not connect DURApulse drives to
grounded, center-tapped delta transformers (which are typically used for lighting circuits).
460V Class – Three Phase
Model Name: GS3-xxx 41P0 42P0 43P0 45P0 47P5 4010 4015
Output
Rating
Maximum Motor
Output
HP
1 2 3 5 7.5 10 15
kW
0.75 1.5 2.2 3.7 5.5 7.5 11
Rated Output Current (A)
2.7 4.2 5.5 8.5 13 18 24
Maximum Output Voltage
Three-phase 380 to 480V (proportional to input voltage)
Rated frequency
0.1 to 400 Hz
* Input
Rating
Rated Voltage/Frequency
Three-phase,
380/400/415/440/460/480VAC; 50/60 Hz
Rated Input Current (A)
3.2 4.3 5.9 11.2 14 19 25
Voltage/Frequency Tolerance
Voltage: ± 10% Frequency: ± 5%
Short Circuit Withstand
(SCCR) (A, rms symmetrical)
5kA @ 480 VAC
Watt Loss 100% I (W)
70 102 132 176 250 345 445
Weight (lb [kg])
3.9
[1.759]
4.4
[1.994]
4.1
[1.857]
9.4
[4.24]
13.2
[6.002]
13.5
[6.106]
14.4
[6.525]
* All 3-phase power sources must be symmetrical. Do not connect DURApulse drives to
grounded, center-tapped delta transformers (which are typically used for lighting circuits).
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013