3–7
Parameter Setup
In order to meet the needs of this application, the parameters should be set as follows:
Motor Nameplate Voltage Setting: 460
Range: 230V series: 200/208/220/230/240 Default Setting: 240
460V series: 380/400/415/440/460/480 Default Setting: 480
This parameter setting is determined by the motor nameplate.
Motor Nameplate Amps Setting: 2.6
Range: Drive Rated Amps x .1 to Default Setting: Drive Rating (A)
Drive Rated Amps x 1.0
This parameter setting is determined by the motor nameplate..
Motor Base Frequency Setting: 60
Range: 50/60/400 Default Setting 60
This parameter setting is determined by the motor nameplate.
Motor Base RPM Setting: 1725
Range: 375 to 24,000 RPM Default Setting: 1750
This parameter setting is determined by the motor nameplate.
Motor Maximum RPM Setting: 2000
Range: P0.03 to 24,000 RPM Default Setting: P0.03
This parameter setting is determined by the needs of the application.
Stop Methods Setting: 00
Range: 00 Ramp to Stop Default Setting: 00
01 Coast to stop
The application requires that this parameter be set to Ramp to Stop
because the motor needs to stop under power. (If the AC drive is set for
Coast to Stop, the AC drive will ignore the Deceleration Time setting.)
WARNING: If the Stop Method for the DURAPULSE AC drive is set for Coast to Stop,
the AC drive will ignore the (P1.02) setting for Deceleration Time.
P1.00
WARNING: The Motor Maximum RPM parameter (P0.04) should never exceed the
maximum RPM rating for the motor that you are using. If this information is not
readily available, consult your motor manufacturer.
P0.04
P0.03
P0.02
P0.01
P0.00
Chapter 3: Keypad Operation and Quickstart
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013