4–17
Motor Line-to-Line Resistance R1 Default: 00
Range: 00 to 65535 milliohm
The motor auto detection feature will set this parameter. The user may also set
this parameter without using P0.05. Some motor manufacturers list this value on
the motor nameplate.
Motor No-Load Current Default: Drive Rated Amps x 0.4
Range: Drive Rated Amps x 0.0 to 0.9 (Amps)
The rated current of the AC drive is regarded as 100%. The setting of the motor
no-load current will affect the slip compensation. The setting value must be less
than the Motor Rated Current (P0.01).
P0.07
P0.06
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013