4–19
Accel S-Curve Default Setting: 00
Range: 00 to 07
This parameter is used whenever the motor and load need to be accelerated more
smoothly. The Accel S-Curve may be set from 0 to 7 to select the desired
acceleration S Curve.
Accel / Decel times 1 and 2 are applied to S-curve calculations.
S-curves can only be seen when the motor is loaded. Static testing will result in no
noticeable change on tuning software (i.e. GSoft).
Decel Time
1 or 2
Accel Time
1 or 2
S-curve
characteristics
Time
S-curve
characteristics
Time
Time
Time
Frequency
P 1.03 = 00
"Accel S curve Disabled"
P 1.04 = 00
"Decel S curve Disabled"
P1.03
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013