In case of changing input
sensor type [
IN-T
], it changes
automatically as max./min. value
of the changed input sensor.
※
For indicator model (TC4
-N N),
only
OFF
,
LOC1
are available.
※
Operates only selected output between Relay or SSR.
※
When changing control output operation,
ErMU
is initialized.
※
When changing control type,
ErMU
is initialized (control output
MV is below 100%) and
DI-K
turns OFF automatically.
※
It is displayed when selecting control output [
OUT
] as
SSR
.
For AC/DC power type (TC4
- 2R), this parameter [
SSrM
]
is not displayed.
※
Press
key to convert alarm
operation mode into alarm option.
※
Refer to page H-62.
※
Same with the above [
AL-1
].
※WhenchangingalarmoperationAL1,AL2alarmtemperatureof
AL1,AL2isinitialized.
Setting range:0.5 to 120.0 sec.
※
If control output [
OUT
] is set as
RLY
, factory default is 20.0 sec, or set as SSR drive output
[
SSR
], factory default is 2.0 sec.
※This
T
willnotbedisplayedwhenSSRdriveoutputmethod
[
SSrM
] is set as
CYCL
,
PHAS
.
Setting range: 1 to 100
℃/℉
(
DPtL
/
CYsL
: 0.1 to 50.0
℃
)
※
If AL1, AL2 alarm operation [
AL-1
,
AL-2
] is set to
AM)_
,
SBa
,
LBA
,
AHYS
parameter is
not displayed.
Setting range: 0.0 to 100.0%
※
0.0/100.0% is displayed when control type parameter [
C-MD
] is set
ONOF
.
※WhenchangingPIDcontroltoON/OFFcontrol,ifMVisbelow100.0%,itisinitializedas0.0%.
※
AlRE
isnotdisplayedfornotalarmoutputmodel.
※
AT
isnotdisplayedwhencontroltypeparameter[
C-MD
]isset
ONOF
.
Setting range: 0 to 9999sec. (Automatically setting with Auto-tuning)
※
LBaT
parameter is displayed when AL1, AL2 alarm operation [
AL-1
,
AL-2
] is set as
LBA
.
Setting range: 0 to 999
℃/℉(
DPtL
/
CUs
: 0.0 to 999.9
℃/℉
)
(automatically setting with auto-tuning)
※
When alarm operation mode [
AL-1
,
AL-2
] is set as loop break alarm (LBA) [
LBA
], and
LBaT
parameter does not set as 0,
LBaB
parameter is displayed.
Setting range: Within the rated temperature range by
input sensor [
L-SV
≤ (
H-SV
-1digit)]
※
When changing SV low-limit value, if SV<
L-SV
, SV is
initialized as
L-SV
.
Setting range: Within the rated temperature range by
input sensor [
H-SV
≥ (
L-SV
+1digit)]
※
When changing SV high-limit value, if SV>
H-SV
,
SV is
initialized as
H-SV
.
SV low-limit value
SV high-limit value
Control output operation
Control type
Control output type
SSR dirve output method
Control cycle
AL1 alarm operation
AL2 alarm operation
Alarm output hysteresis
LBA monitoring time
LBA detection band
Digital input key
Control output MV in case
of input break error
Parameter lock
※
Alarm operation
※
Alarm option
L-SV
H-SV
O-FT
C-MD
OUT
LOC OFF LOC1 LOC2 LOC3
ErMV 00)0
DI-K
002
0
00I
AM@A
SSrM
T
AL-1
AL-2
AHYS
LBaT
LBaB
-050
1200
HEAT
PID
RLY
STND
02)0
AMiA LBaA
AM!A AMiB
COOL
ONOF
SSR
CYCL PHAS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
STOPOFF AlRE AT
Press + keys for 3 sec. and it executes
the set function. For more information, refer to
Functions '
Digital input key'.