Panel Inputs and Outputs
System Description, Autroprime Interactive Fire Detection System, 116-P-APRIME-SYSTEMD/XGB 2007-10-10,
Autronica Fire and Security AS
Page 21
4. Panel Inputs and Outputs
4.1.1 Main Terminal Block J1
Det.Loop2 in - 32
Det.Loop2 in + 31
Det.Loop2 out - 30
Det.Loop2 out + 29
For connection of
Max 127 detectors/loop units
Det.Loop1 in - 28
Det.Loop1 in + 27
Det.Loop1 out - 26
Det.Loop1 out + 25
For connection of
Max 127 detectors/loop units
Rel.Outp.2 NC 24
Rel.Outp.2 NO 23
Rel.Outp.2 Com 22
Default configured as
Fault Warning Routing Equipment.(FWRE)
Potential free changeover contact.
Non-monitored. Max.30VDC/1A
Rel.Outp.1 NC 21
Rel.Outp.1 NO 20
Rel.Outp.1 Com 19
Default configured as
Fire Alarm Routing Equipment.(FARE)
Potential free changeover contact.
Non-monitored. Max. 30VDC/1A
Aux1 +24V out 18
Supply voltage for loads connected to
Open collector outputs 1 and 2. Max.1A
Open Collector
Output 2
17
User configurable Open collector output.
Non-monitored
Switches to 0V at activation. Max.0,5A
Open Collector
Output 1
16
User configurable Open collector output.
Non-monitored
Switches to 0V at activation. Max.0,5A
Mon.Outp.2 0V 15
Mon.Outp.2 +24V 14
Mon.Outp.1 0V 13
Mon.Outp.1 +24V 12
Default configured as Fire Alarm Device
Output. Monitored for short and open circuit. 2kohm end resistor. Max 500mA
Mon.Inp.0V 11 0V reference for Monitored Inputs 1 & 2
Mon.Inp. 2 10
User configurable input. Monitored for open and short circuit.2k resistor to 0V.
Activates at 910 ohm to 0V
Mon.Inp. 1 9
User configurable input. Monitored for open and short circuit.2k resistor to 0V.
Activates at 910 ohm to 0V
Aux2 0V out 8
Aux2+24V out 7
Power to panel bus.
Max 1A (Fuse F4)
Aux1 0V out 6
Aux1+24V out 5
Power to panel bus.
Max 1A (Fuse F1)
(includes output 18)
Charger 0V 4
Charger +24V 3
For connection of internal charger
Battery - 2
Battery + 1
For connection of standby battery
Fuse F2, 5A