System Characteristics
System Description, Autroprime Interactive Fire Detection System, 116-P-APRIME-SYSTEMD/XGB 2007-10-10,
Autronica Fire and Security AS
Page 6
2.4 Compliance with Regulations and Standards
Autroprime complies with C.E.N. EN 54 regulations, FM regulations
(Factory Mutual) and the maritime SOLAS requirements (Safety Of
Life At Sea).
2.5 EN 54-2 Functionality List
With reference to 12.2.1 in EN 54-2.
h) a general description of the equipment, including a list of the:
optional functions with requirements of this European Standard
(chapter
2.5.1 in this handbook)
functions relating to other parts of EN 54 (chapter
2.5.2 in this
handbook)
ancillary functions not required by this European Standard (chapter
2.5.3 in this handbook)
2.5.1 Optional functions with requirements of this European Standard
EN 54-2
Clause
Imple-
mented
Option text Description/Requirement Autroprime functionality
7.8 Yes Output to Fire
Alarm
Device(s)
Automatic transmission of fire
alarm signals to fire alarm
devices.
7.9 Yes Output to Fire
Alarm
Routing
Equipment
Automatic transmission of fire
alarm signals to fire alarm
routing equipment.
Indicated by separate light
emitting indicator.
7.10 Yes Output to Fire
Protection
Equipment
Transmission of fire alarm
signals to controls for automatic
fire protection equipment.
Output type A
7.11 Yes Delays to
outputs
Delay the actioning of outputs to
fire alarm devices and/or fire
alarm routing equipment.
Prepared through
configuration.
Entering Day-mode (input
or menu) activates delays.
Manual call points may
override delays.
7.12 Yes Dependency
(Type C)
Inhibit either the indication fire
alarm condition, or the operation
of outputs, until confirmatory
signals are received.
Detection zone configured
as ‘Dependency’.
Panels will indicate fire
alarm condition. Outputs
inhibited until confirmatory
signals. Manual call points
overrides co-incidence.
7.13 No Alarm
counter
Record the number of instances
that the c.i.e. enters the fire
alarm condition.
Search ‘filters’ in Log may
give alarms or resets only
(with date/time).
8.3 Yes Fault signal
from points
Faults shall be indicated at least
as zone faults.
Interpreted to be better to
give detailed point info.
8.4 No Total loss of
power supply
An indication shall be given for a
period of at least one hour.
8.9 Yes Output to
Fault
Warning
Routing
Equipment
Transmission of fault signals to
fault warning routing equipment.
9.5 Yes Disablement
of
addressable
points
Disabling and enabling points
individually, or in groups, by
manual operation.
If all points within a
detection zone are
disabled, the indication
changes to zone
disablement.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autroprime BS-200M and is the answer not in the manual?

Autronica Autroprime BS-200M Specifications

General IconGeneral
BrandAutronica
ModelAutroprime BS-200M
CategoryFirefighting Equipment
LanguageEnglish

Related product manuals