Panel Inputs and Outputs
System Description, Autroprime Interactive Fire Detection System, 116-P-APRIME-SYSTEMD/XGB 2007-10-10,
Autronica Fire and Security AS
Page 22
4.1.2 Auxiliary Terminal Block J4
1 RS232 Tx
2 RS232 Rx
3 RS232/485 0V
4 RS422/485 A
5 RS422/485 B
6 RS422 Z
7 RS422 X
External Interface
Optional data lines
8 O.P.Output +24V
9 O.P.Output 0V
10 O.P.Output A
11 O.P.Output B
12 O.P.Input +24V
13 O.P.Input 0V
14
O.P.Input A
15 O.P.Input B
Connections to Operator Panel
(Return/Input for redundancy)
16 BU/BV Output A
17 BU/BV Output B
18 BU/BV Input A
19 BU/BV Input B
Connections to panel bus. Connects from unit to
unit.
(Return/Input for redundancy)
20
Non-monitored inp.1
+
21
Non-monitored inp.1
-
User configurable input
Activates at application of 24VDC.
Observe polarity
22
Non-monitored inp.2
+
23
Non-monitored inp.2
-
User configurable input
Activates at application of 24VDC.
Observe polarity
4.1.3 User Configurable Inputs
User configurable inputs can be used for
Day/Night input
User Configurable input
Morse input
Mute Fire Alarm Device (FAD) input
Reset in
Silence in
Fire Alarm Routing Equipment (FARE) feedback (signal from fire
brigade)
Activate all alarms
Monitored Fault Warning Routing Equipment, FWRE
4.1.4 User Configurable Outputs
User configurable outputs can be used for
User Configured output (or General output)
Reset Out
Silence Out
Disable Out
Silent Alarm Out
Small Alarm Out
Fire Alarm Device, FAD
Fire Alarm Routing Equipment, FARE
Fault Warning Routing Equipment, FWRE