AUX DC Inverter Free Match 50HZ R32
187
Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or
leakage etc.
The unit has a drain pump which will lift up to 700 mm. However after the pump stops the
water left in the pipe will drain back and may overflow the drain tray causing water leakage. For
this reason please install the drain pipe as shown
When draining multiple units into a common drain line, this common drain should be installed
about 100mm below each units drain outlet, as shown in the drawing.