EasyManua.ls Logo

Azbil AMT - Gasket Section Liquid Leak; Downstream Leaks When Closed

Azbil AMT
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Azbil Corporation
Model: AMT, HDT - CV3000 Series Control Valves
54
Symptom Cause and Remedy
Even when valve plug is in closed
position, large flow leaks to
downstream side.
Air leak at actuator section.
For trial, apply the air supply pressure or atmospheric pressure to the
actuator. (Check the air supply source and positioner.)
Check whether the valve plug is actually the closed position or not.
(Check the valve plug lift)
Check the plug seat ring for corrosion and erosion.
Check the guide sections for binding.