EasyManua.ls Logo

Azbil AUR355 - Specifications; RS-485 Specifications

Azbil AUR355
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
Chapter 7. Specifications
Item Description
General
specifications
Protective
structure
IP40: if sideboards (81447515-001) are attached to the sub-base (model BC-R05)
IP10: (sub-base (model BC-R05) only)
Overvoltage
category
II
Pollution degree PD2
Automatic action Type 2.A.V
Software Class C
Case color Black
Case material Denatured PPE resin (UL 94-V0 PTI materials group IIIa)
General
specifications
Structure Sub-base and main unit
Mounting
orientation
Vertical or horizontal
For horizontal mounting, the 7-segment display must face upward (DIN rail mounting or
direct mounting through screw holes in base)
Standards
compliance
JIS C 9730-2-5:2010 (Automatic Electrical Controls for Household and Similar Use - Part
2-5: Particular Requirements for Automatic Electrical Burner Control Systems)
JIS C 9730-1:2010 (Automatic Electrical Controls for Household and Similar Use - Part 1:
General Requirements)
Dimensions W95 × H105 × D110 mm (incl. sub-base)
Weight Approximately 600 g (incl. sub-base)
Wiring types and max.
wiring length
Start
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
,
recommended length: 20 m or less, max. wiring length: 100 m
Contact reset
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
,
recommended length: 20 m or less, max. wiring length: 100 m
AUD300C/500C (F, G, S1, S2)
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
, max. wiring length: 200 m
Flame rod (F, G)
RG-11U (JAN standard: US DoD compliant specification) or the equivalent, 5C2V,
7C2V (JIS standard)
Recommended length: 20 m or less, max. wiring length: 30 m
RS-485 communications (3-wire system)
0.2–1.5 mm
2
shielded, twisted pair cable (recommended), max.
wiring length: 500 m
Flame voltage output signal
Copper 600 V PVC-insulated cable (IEC 60227-3), 0.75 mm
2
min.,
max. wiring length: 10 m
Event output
JIS C 3306: 0.75 mm
2
min.
Flame relay N.C. output
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
Flame output (with start check)
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
Flame output
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
* Contact reset input (terminal 24) (p.18) (for details on the contact reset input specifications)