5-85
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
 Setting example
•  Event
Event Display Internal Event 1 Internal Event 2
Operation type
E
_ 
.C1
9:  Deviation high/low 
limit (Final SP reference)
32: Timer (Status)
Direct/reverse
E
_ 
.C2
1: Reversed. ----
Standby
E
_ 
.C2
0: No standby ----
EVENT state at READY
E
_ 
.C2
1:  EVENT state at READY is 
forcibly turned OFF.
0:  EVENT state at READY is 
continued.
Alarm OR
E
_ 
.C3
0: None 0: None
Special OFF setup
E
_ 
.C3
0: As usual. ----
Delay time unit
E
_ 
.C3
0: 0.1s 0: 0.1s
Event main setting 
(low limit)
E
_ 
3 ----
Event sub setting 
(high limit)
E
_ 
.SB
3 ----
Hysteresis
E
_ 
.HY
9999 ----
ON delay
E
_ 
.ON
2 15
OFF delay
E
_ 
.OF
0 0
Note.   The internal event No. is indicated at the mark of "_" shown in the display 
column.
•  DI Assignment
DI Assignment Display Internal Contact 1 Internal Contact 2
Operation type
DI
 _ 
.1
7: RUN/READY 17: Timer stop/start
Input bit function
DI
 _ 
.2
1:  Function 1 (A and B) or 
(C and D)
1:  Function 1 (A and B) or 
(C and D)
Input assignment A
DI
 _ 
.3
18: COM DI 1 10:  Internal Event 1 
(Setting = 9: Deviation 
high/low limit (Final 
SP reference)
Input assignment B
DI
 _ 
.4
11:   Internal   
Event 2 (Setting = 32: 
Timer (Status))
26: During SP ramp
Input assignment C
DI
 _ 
.5
0:  Normally opened. 
(Normally Off = 0)
18: COM DI 1
Input assignment D
DI
 _ 
.6
0:  Normally opened. 
(Normally Off = 0)
11:  Internal Event 2 
(Setting = 32:  
Timer (Status))
Polarity A
DI
 _ 
.7
0: Direct 0: Direct
Polarity B
DI
 _ 
.7
1: Reverse 1: Reverse
Polarity C
DI
 _ 
.7
0: Direct 0: Direct
Polarity D
DI
 _ 
.7
0: Direct 0: Direct
Polarity
DI
 _ 
.8
1: Reverse 0: Direct
Event channel 
definitions
DI
 _ 
.9
---- 2
Note.   The internal DI No. is indicated at the mark of "_" shown in the display 
column.