5-86
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
 Others
C72
 [mode key function]:  7 (COM DI1 selection)
SP ramp-up/ramp-down:  Desired value
 Setting points
The internal EV1 is substituted for the guarantee soak.
Therefore, “9999” is set to the hysteresis of Event 1 so that Event 1 is not turned 
OFF after it has been turned ON even though the PV fluctuates.
DI Assignment (Internal Contact 1): Input/Output port setup
Logical AND of COM DI1 (A-contact) 
and timer (B-contact)
Mode (RUN/READY) selection 
contact
Reversed at this point since the 
mode is the READY mode when 
turned ON.
DI Assignment (Internal Contact 2):  Input/Output port setup
The timer start is self-retained at time-up so that 
the timer is not restarted due to change in PV.
Timer start-up contact
Conditions for guarantee soak (ramp is completed and operation enters 
within the deviation of the nal SP.)