5-16
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
MANUAL mode change
The control output when the AUTO mode is changed to the MANUAL mode can 
be set.
Item (Bank) Display Contents Initial value User level
Output operation at 
changing Auto/Manual 
(Setup bank)
0: Bumpless transfer
1: Preset
0 Standard, 
High function
Preset MANUAL value 
(Setup bank)
-10.0 to +110.0% 0.0 or 50.0% Standard, 
High function
•  When [
C
19
: Output operation at changing Auto/Manual] is set at [0: Bumpless 
transfer], the manipulated variable (MV) when the AUTO mode is changed to 
the MANUAL mode is retained. When set at [1: Preset], the manipulated variable 
(MV) is set to [
C20
: Preset MANUAL value] when the AUTO mode is changed to 
the MANUAL mode.
•  When the control method is other than ON/OFF control (
CtrL
 ≠ 0), [
C
19
: 
Output operation at changing Auto/Manual] and [
C20
: Preset MANUAL value] 
can be displayed and set.
•  When the Heat/Cool control is not used (
C26
 = 0), the initial value of [
C20
: 
Preset MANUAL value] is [0.0].  On the contrary, when the Heat/Cool control is 
used (
C26
 = 1), this initial value becomes [50.0].
  Handling Precautions
When the unit is in the MANUAL mode if the power is turned ON, the set 
value of 
C20
 becomes the initial manipulated variable (MV).
PID control initialization
Item (Bank) Display Contents Initial value User level
Initial output type (mode) 
of PID control 
(Setup bank)
0: Auto
1: Not initialized.
2:  Initialized. (If SP value different from the 
current value is input.)
0 High function
•  When the control method is other than the ON/OFF control (
CtrL
 ≠ 0), the 
display and setting can be performed.
•  If the PID group is changed as the SP value or SP group is changed, the 
manipulated variable (MV) is stopped at its low limit or high limit, and then the 
PV may not change or may overshoot.  To prevent such trouble, it is effective to 
initialize the PID control.
•  The setting is “0” (Auto). 
It is judged automatically whether or not the PID control needs to be initialized 
as the SP value or SP group is changed.  As a result, the PID control is initialized 
only when it is required.
•  The setting is “1” (Not initialized). 
Even though the SP value or SP group is changed, the PID control is not 
initialized.  This setting is effective when the continuation of the manipulated 
variable (MV) is important if the SP value or SP group is changed.
•  The setting is “2” (Initialized). 
Every time the SP value or SP group is changed, the PID control is always 
initialized.  This setting is effective when it is important that an increase or a 
decrease in manipulated variable (MV) immediately affects the relationship 
between the PV and SP when the SP value or SP group is changed.