EasyManuals Logo

B meters HYDRODIGIT User Manual

B meters HYDRODIGIT
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
7
User Manual v1.4.3
HYDRODIGIT
It is possible to change the configuration parameters into Walk-By mode with an USB to IR interface (B
METERS mod. UC-Cable) and the B Metering software.
Walk by mode parameters:
• Transmission frequency: every 60 seconds (current values).
• Transmission span: Every day from 6 to 20.
• Encryption: enabled/disabled.
• Historical Data (12 months).
Transmitted data: Volume, actual date and hour, reverse flow, alarms, leakage date, fraud date (Qmax
overflow or Backward flow detection).
Wireless MBUS OMS v4 (COMBO, output conguration Wireless MBUS OMS v4 only)
As soon as radio operation mode is activated, the meter sends a radio telegram according to Wireless
MBUS OMS v4, T1 mode (unidirectional transmission).
Preconfigured Radio parameters (AMR Mode):
• Transmission frequency: every 200 seconds (current values).
• Transmission span: Every day, from 0 to 24 h.
• Encryption: disabled (default).
• No historical data.
• Transmitted data: Volume, actual date and hour, reverse flow, alarms.
It is possible to change the configuration parameters into Walk-By mode with an USB to IR interface (B
METERS mod. UC-Cable) and the B Metering software
• Transmission frequency: configurable (minimum 60 seconds).
Transmission interval: from Monday to Sunday, maximum 12 hours per day (time slot can be selected freely).
 Possibility to select a 24-hours time slot with the following mandatory conditions:
       Transmission frequency: > 300 seconds
       Historical data disabled.
• Encryption: enabled/disabled.
• Historical data (12 months).
• Transmitted data (depends on the selected parameters): volume, date time, reverse flow, alarms, leakage
alarm, fraud alarm (Qmax overflow or backward flow detection).
LoRaWAN (COMBO, output conguration LoraWAN only)
As soon as radio operation mode is activated, the meter sends join requests to the Network Server where it
has been provisioned, according to LoRaWAN transmission standard.
During this process, the radio icon on the display will blink every second. If the procedure ends well, the icon
will remain on and stable, otherwise it will turn off.