1. Water deflection plates
2. Water holes
3. Activate the pre-cooler water from the digital controller's maintenance menu to verify if any holes are clogged
and need cleaning. If water is spraying out of the tube (+/- 10 cm high) at regular intervals, all holes are free.
This applies to both drain holes at the extremities of the distribution pipe as well.
4. Unscrew the cap at the end of the tube to flush any debris that might be caught in the water distribution pipe.
1. Cap on water distribution tube
5. After the tube is flushed, stop the flow of water by exiting the maintenance menu. Put everything back in place
in the reverse order. Close the cover by gently lifting the securing hook.
When reinstalling the water deflection plates, make sure to slide the rubbers to the side in order to provide
a proper seal as indicated in the following picture.
1. Side rubbers on the water distribution tube
W W W . B A L T I M O R E A I R C O I L . E U