2. Lift the pump out of the strainer and remove it through the inspection panel.
3. Remove the bolts securing the strainer in the sump to remove this as well in order to clean it outside of the unit.
4. Reinstall in the reverse order.
Adiabatic pre-cooling media
CLEANING
The digital controller provides automatic periodic cleaning of the pre-cooling media.
If the media need additional manual cleaning, a cleaning cycle can be forced through the controller.
REMOVAL AND REPLACEMENT
The expected service lifetime of the pre-cooling media is 5 to 7 years if basic housekeeping practices and these
operating and maintenance guidelines are followed. If severe disposition causes reduced humidification efficiency
and reduced airflow, it is recommended that the pre-cooling media is replaced. New adiabatic pre-cooling media
are available from your local BAC-Balticare representative.
Media removal/replacement procedure:
1. Verify that the pre-cooling media are DRY! Removing a wet pad will create debris falling into the unit.
2. Remove top plate.
W W W . B A L T I M O R E A I R C O I L . E U
24

Other manuals for BAC Trillium Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BAC Trillium Series and is the answer not in the manual?

BAC Trillium Series Specifications

General IconGeneral
BrandBAC
ModelTrillium Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals