GENERAL INFORMATION
Operating conditions
BAC cooling equipment is designed for the operating conditions specified below, which must not be exceeded
during operation.
• Wind Load: For safe operation of unshielded equipment exposed to wind speeds above 120 km/h installed at a
height above 30 m from the ground, contact your local BAC-Balticare representative.
• Seismic Risk: For safe operation of equipment installed in moderate and high hazard area's contact your local
BAC-Balticare representative.
Ambient temperature at continuous full speed; full load operation ranges from -10°C to+45°C. For cold climates, if
optional thermostatically controlled heaters are employed, the temperature range can be extended from -40°C
to+45°C.
HEAT EXCHANGER COIL
• Design pressure: 10 bar
• Maximum fluid inlet temperature: 60 °C
• Fluids circulated through the inside of the coils must be compatible with the coil construction material.
ADIABATIC PRE-COOLER OF TRILLIUMSERIES COOLER
• Design water supply pressure: 3-10 bar
• The water distributed on the adiabatic pre-coolers should be of potable supply.
• In case of non-treated water, the temperature should be kept below 20°C.
Connecting pipework
All piping external to BAC cooling equipment must be supported separately.
In case the equipment is installed on vibration rails or springs, the piping must contain compensators to eliminate
vibrations carried through the external pipework.
The equipment outlet piping must be installed under the operating level of the equipment to prevent air suction and
pump cavitation.