DANGER
• DANGER: Do not perform any service on or near the fans, motors, and drives, without first ensuring that the fans are disconnected, locked out,
and tagged out.
• WARNING: Failure to use designated lifting points can result in a dropped load causing severe injury, death, and/or property damage. Lifts
must be performed by qualified riggers following BAC published Rigging Instructions and generally accepted lifting practices. The use of
supplemental safety slings may also be required if the lift circumstances warrant its use, as determined by the rigging contractor.
• WARNING: Only personnel qualified to do so should undertake the installation, operation, maintenance and repair of this equipment. Proper
care, procedures, and tools must be used in handling, lifting, installing, operating, maintaining, and repairing this equipment to prevent
personal injury and/or property damage.
• WARNING: To prevent possible contamination of the make-up water supply, install a backflow prevention method in accordance with applicable
local and national codes.
• WARNING: The top horizontal surface of the unit is not intended to be used as a walking surface or working platform. If access to the top of the
unit is desired, the purchaser/end-user is cautioned to use appropriate means complying with applicable safety standards of governmental
authorities.
• WARNING: All electrical, mechanical, and rotating machinery are potential hazards, particularly for those not familiar with their design,
construction, and operation. Accordingly, use appropriate lockout procedures. Adequate safeguards (including the use of protective enclosures
where necessary) should be taken with this equipment both to safeguard the public from injury and to prevent damage to the equipment, its
associated system, and the premises.
• WARNING: Incoming power lines to the disconnect switch remain energized. Take proper electrical precautions when working near energized
equipment.
• WARNING: The TrilliumSeries™ Adiabatic Product controls are set up to periodically flush and drain the water system, thereby eliminating the
need for water treatment. However there may be unusual circumstances where chemicals or biological contaminants could be introduced into
the recirculating water system, which could be harmful if inhaled or ingested. If there is a concern that this has happened, wear appropriate
respiratory protection as a precaution, when exposed to the discharge air stream or to the mists produced by cleaning activities associated with
the recirculating water system or Pre-Cooler Pads.
• CAUTION: The operation, maintenance, and repair of this equipment shall be undertaken only by personnel authorized and qualified to do
so. All such personnel shall be thoroughly familiar with the equipment, the associated system and controls, and the procedures set forth
in this manual. Proper care, personal protective equipment, procedures, and tools must be used in handling, lifting, installing, operating,
maintaining, and repairing this equipment to prevent personal injury and/or property damage.
• BAC units are typically installed immediately after shipment and many operate year round. However, if the unit is to be stored for a prolonged
period of time either before or after installation, certain precautions should be observed.
• Do not run the unit wet with the pre-cooler pads out and the fans on (thereby getting the coils wet). Wet/dry cycling of the unit this way could
shorten the coil life, and voids the warranty.
• Before an actual lift is undertaken, open the access hatch(es) and check to ensure no water, snow, ice, or debris has collected in the sump or
elsewhere in the unit. Such accumulations will substantially add to the equipment’s lifting weight.
• When connecting power to the unit, do not penetrate the top of the control panel. Doing so may allow moisture to enter the panel. All cable and
conduit should be supported separately from the unit. Do not penetrate the unit for supports or other connections.
• Do not use steam, high pressure water, or high pressure air to clean any component.
• Do not attempt to remove the Pre-Cooler Pads while wet to prevent excessive degradation.
WARNING
NOTICE