17
Installation
Water Connection
Installation of the Pressure
Regulating Valve
Ammonia Installation
Instructions
Customer Electrical
Connections
Wiring and Electrical Information
For the diagram showing customer power and control signal input connections, refer to the
submittal package. This information is also in a package on the inside of the control panel.
NOTE:
FLA = Full Load Amps
MCA = Minimum Circuit Ampacity
MOP = Maximum Overcurrent
Protection
Table 4. FLA, MCA and MOP Ratings (amps) for 60 Hz Three Phase Power
Model Number Fan Qty. Pump Qty. FLA MCA MOP
460V
TSDC-xxx-3 1 1 4.7 5.9 15
TSDC-xxx-6.2 2 1 8.7 10.8 15
TSDC-xxx-9.6 3 1 12.6 15.8 20
TSDC-xxx-12.4 4 1 16.6 20.7 25
TSDx2-xxx-xxx-12.4 4 2 16 20 25
TSDx2-xxx-xxx-18.6 6 2 23.3 29.1 30
TSDx2-xxx-xxx-24.8 8 2 30.6 38.2 40
TSDx2-xxx-xxx-31.0 10 2 37.9 47.3 50
TSDx2-xxx-xxx-37.2 12 2 45.1 56.4 60
TSDx2-xxx-xxx-43.4 14 2 52.4 65.5 70
380V
TSDC-xxx-3
1 1 5.7 7.1 15
TSDC-xxx-6.2
2 1 10.5 13.1 15
TSDC-xxx-9.6
3 1 15.3 19.1 20
TSDC-xxx-12.4
4 1 20.1 25.1 30
TSDx2-xxx-xxx-12.4
4 2 19.4 24.3 25
TSDx2-xxx-xxx-18.6
6 2 28.2 35.3 40
TSDx2-xxx-xxx-24.8
8 2 37 46.3 50
TSDx2-xxx-xxx-31.0
10 2 45.8 57.3 60
TSDx2-xxx-xxx-37.2
12 2 54.6 68.3 70
TSDx2-xxx-xxx-43.4
14 2 63.5 79.3 80
230V
TSDC-xxx-3
1 1 9.6 12 15
TSDC-xxx-6.2
2 1 17.8 22.2 25
TSDC-xxx-9.6
3 1 25.9 32.4 40
TSDC-xxx-12.4
4 1 34 42.5 50
TSDx2-xxx-xxx-12.4
4 2 31.6 39.5 40
TSDx2-xxx-xxx-18.6
6 2 45.9 57.4 60
TSDx2-xxx-xxx-24.8
8 2 60.2 75.3 80
TSDx2-xxx-xxx-31.0
10 2 74.6 93.2 100
TSDx2-xxx-xxx-37.2
12 2 88.9 111.1 125
TSDx2-xxx-xxx-43.4
14 2 103.2 129 150
200V
TSDC-xxx-3
1 1 11.2 14 20
TSDC-xxx-6.2
2 1 20.6 25.7 30
TSDC-xxx-9.6
3 1 30 37.5 40
TSDC-xxx-12.4
4 1 39.4 49.2 50
TSDx2-xxx-xxx-12.4
4 2 36.5 45.6 50
TSDx2-xxx-xxx-18.6
6 2 52.9 66.2 70
TSDx2-xxx-xxx-24.8
8 2 69.4 86.8 90
TSDx2-xxx-xxx-31.0
10 2 85.9 107.4 110
TSDx2-xxx-xxx-37.2
12 2 102.4 127.9 150
TSDx2-xxx-xxx-43.4
14 2 118.8 148.5 150