WWW.BALTIMOREAIRCOIL.COM
52
2. Information: This submenu allows the user to view the software version, the BIOS, and
the dates of the latest update.
3. Manual Control: This submenu allows the user to manually control the valves, the fans,
the pump, and all other analog and digital inputs and outputs. Note, after 15 minutes
in inactivity, the controller will revert back into automatic operation of the components.
The following items can be manually controlled:
Fans
Water Pump
Dump Valve
Make-up Valve
General Alarm
Outside Air Temperature
Float Switch
Pre-Cooler Mode
Pump Proof - a current detecting switch on the pump; it closes if the pump runs
and signals to the controller that the pump draws power
4. Clock: This submenu will allow the user to set the date and time on the controller.
Datalogging
If you have purchased the Energy Monitoring Package with your TrilliumSeries™ Adiabatic
Product, the EcoFlex™ Controls stores historical data from the unit and make it available
for downloading using a USB flash drive. The parameters are recorded every 10 minutes
(adjustable). When the total memory of the controller is 90% used, the new data override
the oldest set of data. Datalog files are stored in an excel format. Datalog inputs are
selectable from the interface screen.
The following parameters are recorded:
Date and time of day
Outside Air Temperature
Fan Speed
Pump Status
Make-up valve position
Dump Valve
kW
All alarms
Head Pressure
[1]
(only for units with the Head Pressure Control Package)
Conductivity
[1]
(only for units with the optional Water Monitoring Package)
NOTE:
1. Optional parameters only
recorded if the applicable
feature is purchased.