VIGIL3 Voice Alarm
Overview, Architecture and Configuration
12 VIGIL3 Overview, Architecture & Configuration issue 2
Rules can be triggered by;
A message being triggered or removed from an output
A route being triggered or removed from an output
A BVRDCI Control Output Changing State
A BVRDFPI or BV3FPI input
A BVRDCI Control Input
By a countdown timer started by another Rule
At a specific time
•Hourly
•Daily
Weekdays only
Weekends only
Weekly
Monthly
Annually
The effect of a rule being triggered can be;
Set a volume control
Start or Stop a message to an Output Set
Set a route or clear a route from an Input to an Output Set
•Set or Clear a BVRDCI Control Output
Adjust the system time
Start a countdown timer that then triggers another Rule on
expiry
Cause and Effect rules should be created in order to push “Effects”
out to other BV3AOM8 modules. This will ensure that in the
event of catastrophic system failure (i.e. due to fire damage) the