VIGIL3 Voice Alarm
Overview, Architecture and Configuration
10 VIGIL3 Overview, Architecture & Configuration issue 2
Please see below for a table of the required BDM/BFM
Microphone configuration (stored in the BDM/BFM
microphone).
Table 2.3 — Vigil 2 BDM/BFM required configuration
Config Item Required Setting
Speak Now Delay As required to allow chime to finish
Microphone Address 5
Audio Input Channel Input 5a
Number of routers 1
Mic Surveillance Mic Capsule/Audio/Data
*1
Message Mode All Call
Protocol Type Type 3
*2
Poll Rate 1.0
Baud Rate 9600
*2
Microphone Type As required depending on microphone type
Single Zone, 4/8 Zone or 16 Zone
Repeat Transmission 2
Busy Disable (from) 10
Busy Disable (to) 11
VA Input Active Input 1a to 2a
VA Message Active Message 1 to 2
NOTE:
*1
If fault buzzer is not required the Mic Surveillance can be set
to Mic Capsule/Audio/Data/No Buzzer
NOTE:
*2
Matching configuration must be present in the BV3AIM2/4
module.
2.5 AUDIO PRIORITIES
VIGIL3 systems support a total of 254 priorities that can be
allocated to audio inputs and DVA messages. Priority 1 is the
highest and 254 is the lowest. A higher priority input will
override a lower priority input.
If 2 inputs with the same priority ar
e attempted to be routed to
the same output the system operates on a first come first served
basis.