VIGIL3 Voice Alarm
Overview, Architecture and Configuration
VIGIL3 Overview, Architecture & Configuration issue 2
11
Each audio input has 2 priorities associated with it that
correspond to key turned (Emergency Mode) or key not turned
(Paging) modes.
2.6 VOICE ALARM (VA) ACTIVE INDICATION
VA Active indication is performed based on priority. Any input or
message routed to any output with a Priority between 1 and 64
will cause all system VA Active indicators to illuminate.
2.7 FIRE PANEL INPUTS
Fire panel inputs in a VIGIL3 system can be connected to either
BVRDFPI CAN bus Fire Panel Interface modules or to BV3FPI
Fire Panel Interface Modules.
Facilities are provided for the connection of Fire Panel specific
EOL resistors to enable the fire panel to monitor the connection
to the VIGIL3 System.
Fire Panel inputs can be either continuous or pulsing to indicate
Alert and Evacuate conditions.
2.8 CAUSE AND EFFECT RULE ENGINE
All external triggering (i.e. by a Fire Panel) of message playback
or route setting is controlled by the VIGIL3 Cause and Effect
engine.
The Cause and Effect engine is made up a series of configurable
rules which have a “Cause” (e.g. FPI Input) and an “Effect” (e.g.
Start message playback). Rules act upon Output Sets each of
which can contain any combination of outputs from 1-800.
Each BV3AOM8 can manage up to;
200 Individual Rules
50 Output Sets