EasyManua.ls Logo

Banner DXMR90-4K - Replacing IO-Link Devices During Operation

Banner DXMR90-4K
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 11. RTU Configuration screen for ports 1-4
The DXM Configuration has a special tab for configuring the port settings on the IO-link master. To access go Register
Mapping--> IO-link Configuration. In this section you can configure the port settings of the IO-link Master.
The operating mode can be configured for any port on the IO-Link master. The following modes can be used:
Deactivated
Use deactivated mode for any unused IO-link master ports if a device is not connected.
IO-Link Manual
The IO-Link master only connects IO-Link devices that have a certain vendor ID and device ID (1: IOL_MANUAL).
This mode is also required to for the Backup and Restore or Restore function.
IO-Link Autostart
The IO-Link master connects to every connected IO-Link device (2: IOL_AUTOSTART).
Digital Input
The IO-Link port functions as a standard digital input (3: DI_C/Q).
Digital Output
The IO-Link port functions as a standard digital output (4: DO_C/Q).
For more information on the port settings of the DXMR90-4K IO-Link Master, refer to the DXMR90-4K IO-Link Master Device
Register Map (p/n 209933).
4.3.1 Replacing an IO-Link Device During Operation (Backup/Restore
Mode)
Replacing an IO-Link device during operation is common, and inadvertent changes to device settings can cause operational
problems and down-times. Operating personnel without special knowledge or tools can replace IO-Link devices quickly and
without errors.
When the backup function of the IO-Link master is used, the IO-Link master automatically provides the saved parameters to
the new device after replacement. This makes IO-Link device replacement seamless in IO-Link applications. Another
common industry term for this function is data storage mode.