Clearing the Event Counter
The counter Nodes can clear the counter values from a mapped input signal or from a host system writing to a Modbus register. For
example, a push button on a Gateway can be mapped to Node register 11 to clear a counter when the button is pressed.
From a host system, reset the counter by writing a 1 to Node register 11 for counter 1 or Node register 13 for counter 2.
Setting the counter using the preset or clear functions saves the preset value or zeroes in EEPROM.
Counter Node Menu Structure
CNTR X
(I/O X)
Counter Preset
+1234
SAVED
PRIOR
NADR
To IOCFG
XX
*
DINFO
*
RUN
*
FCTRY
*
DVCFG
*
DERR
Device Info
Factory #s Device Config.
Display Error
56789X
NEW
NADR
XX
CONFIRM
NADR
XX
*
IOCFG
I/O Config
**
*
Counter Node
* If the network address, prior to entering I/O configuration,
is set on the rotary switch setting, the menu system prompts
the user to correct the switch setting before
returning to RUN mode.
** The double word display automatically activates when
more characters are needed.
Single-click
Button 2
Single-click Button 1 to advance through menu
Single-click Button 1 to
advance to next I/O
Single-click
Button 2
Adjust rotary switch to set
the counter preset value
Double-click B1
(backspace)
Double-click
Button 2
Double-click
Button 2
Double-click B2
Single-click
Button 2
Single-click
Button 2
Single-click
Button 2
Single-click B1
Single-click B1
Single-click
Button 2
Single-click B1
Verify Communications
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. Verify LED 1 is green. Until
communication is established with the Gateway, the Node’s LED 2 flashes red. When communication is established, the Node’s LED 1
flashes green.
A Node will not sample its inputs until it is communicating with the Gateway to which it is bound.
LED 1 LED 2 Gateway Status Node Status
(green on)
Power ON
(green flashing)
RF Link OK
(red flashing) (red flashing)
Device Error Device Error
(yellow flashing)
Modbus Communication Active
(red flashing)
Modbus Communication Error No radio link (when flashing
once every three seconds)
For Gateway and Ethernet Bridge systems, active Modbus communication refers to the communication between the Gateway and the
Ethernet Bridge. For GatewayPro systems, the Modbus communication LEDs refer to the communication internal to the Gateway Pro.
For Gateway only systems, the Modbus communication LEDs refer to the communication between the Gateway and its host system (if
applicable).
When testing the Gateway and Node, verify all radios and antennas are at least two meters apart or the communications may fail.
SureCross DX80 FlexPower Node with Counter Inputs
P/N 136348 rev. G www.bannerengineering.com - tel: 763-544-3164 11