TABLE 7
C**H INDOOR BLOWER PERFORMANCE - CFM (0.00" — 0.50" H
2
0)
Model
Rated
ESP
MAX
ESP
k
Blower
Only
Cooling
& Heat Pump
Stage 1
Cooling
& Heat Pump
Stage 2
Electric
Heat
C24H .10 .50 550 550 740 900
C30H .10 .50 650 650 900 900
C36H .15 .50 800 800 1100 1100
C42H .15 .50 800 900 1250 1250
C48H .20 .50 825 1000 1550 1550
C60H .20 .50 850 1300 1650 1650
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately
the same rate of indoor airow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable lter.
k Blower only CFM is the total air being circulated during continuous fan mode. Airow remains constant.
Blower only CFM reduces during continuous fan mode. Requires wiring modication; consult Installation Instructions & Wiring Diagram.
CFM output on Cooling or Electric Heat.