WALL MOUNTED
PACKAGED HEAT PUMP
Models:
INSTALLATION INSTRUCTIONS
C24H1-A
C24H1-B
C30H1-A
C30H1-B
C30H1-C
C36H1-A
C36H1-B
C36H1-C
C42H1-A
C42H1-B
C42H1-C
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-586D
Supersedes: 2100-5486C
Date: 7-28-15
C48H1-A
C48H1-B
C48H1-C
C60H1-A
C60H1-B
C60H1-C

Table of Contents

Questions and Answers

  • H
    Heidi WigginsAug 17, 2025
    Why is the outdoor fan motor not running on my Bard Heat Pump (cooling or heating except during defrost)?
    • D
      deniseortizAug 17, 2025
      If the outdoor fan motor on your Bard Heat Pump isn't running, it could be due to a few reasons. The heat pump control might be defective; check across the fan relay on the heat pump control (Com-NC) and consider replacing the heat pump control. The motor itself could be defective, so check for open or shorted motor windings and replace the motor if necessary. Alternatively, the motor capacitor might be defective, so check the capacitor rating and look for open or shorted capacitors, replacing the capacitor if needed.
  • S
    Samantha WhitakerAug 22, 2025
    What to do if the reversing valve does not energize on my Bard Heat Pump (heating only)?
    • A
      Adrian MillerAug 22, 2025
      If the reversing valve isn't energizing on your Bard Heat Pump, first check for 24V between RV-C and B-C. Make sure to check the control circuit wiring. If that's not the issue, the reversing valve solenoid coil might be defective, so check for an open or shorted coil and replace it if necessary.
  • L
    Linda CooperAug 29, 2025
    How to troubleshoot if my Bard Heat Pump will not go into defrost (heating only)?
    • S
      Scott ArmstrongAug 29, 2025
      If your Bard Heat Pump isn't going into defrost, it could be due to a defective temperature sensor or heat pump control. Try disconnecting the temperature sensor from the board and use a jumper across the "SPEEDUP" and "SEN JMP" terminals. This should initiate a defrost cycle within one minute. If it goes through defrost, replace the temperature sensor. If it doesn't, replace the heat pump control.
  • S
    sarah10Sep 3, 2025
    What to do if my Bard Heat Pump unit will not come out of defrost (heating only)?
    • C
      Carlos MillerSep 3, 2025
      If your Bard Heat Pump won't come out of defrost, the temperature sensor or heat pump control might be defective. Try using a jumper across the "SPEEDUP" terminal. This should cause the unit to exit defrost within one minute. If the unit comes out of defrost, replace the temperature sensor. If it doesn't, replace the heat pump control.
  • M
    Maria HunterNov 10, 2025
    What to do if the Bard Heat Pump compressor will not start in heating or cooling?
    • D
      davilafranklinNov 10, 2025
      If the compressor on your Bard Heat Pump isn't starting, here are a few things you can check: * See if the LED is illuminated on the board. * Check if the LED is flashing a code. * Verify there is 24 volts AC between R and C. * Check what code is blinking. If a compressor delay is active, wait for five minutes or jump the board's "speed up pins". If there's a low or high-pressure fault, check the wiring circuit and unit pressures. Also, check for a compressor input signal by testing for 24 volts AC between Y and C, and check for a compressor output signal by testing for 24 volts AC between CC & C. If there is no "Y" compressor input signal, check the thermostat wiring and unit wiring. If there is no "CC" compressor output signal, check the compressor contactor. If there's no powe...