10. Press Yes or No button to select if humidifier is
present; press Next button.
11. Press Configure to configure any of the following:
Emergency Off alarm, Generator Run alarm, High
Humidity alarm, Dust Alarm, Dehumidification
Active. Press Next or Home button.
System Setup
Menu Descriptions (default indicated in bold)
1. Language – English, French or Spanish
2. Password Protection – User can configure password
here (No)
3. Twinning Staging Logic – Off, All or Pairs
4. Staging Logic – Alternating or non-alternating
5. Lead-Lag Change Over Time – Time setting 0-30
days (7)
6. Continuous Blower Logic – Lead, None, All,
Prepurge or Custom
7. Degrees – Fahrenheit or Celsius
8. Temperature Sensor Logic – Average, highest or
lowest
9. REM 1 Temperature Sensor – Indoor Temperature
or Not Connected
10. REM 2 Temperature Sensor – Indoor Temperature,
Outdoor Temperature or Not Connected
11. Equipment Minimum Run Time – 0-5 minutes (3)
12. Maximum Number of Units While in Generator
Mode – Choice limited to number of HVAC systems
(1).
13. Touch Screen Display Brightness – 10-100% (80)
System Setup Steps
1. Press Setup button on Home screen.
2. Press System Setup button.
3. Press preferred language button; press Next
button.
4. Press Yes button if password protection is desired;
if Yes is selected, a prompt will appear to enter a
PIN number. Press Next button.
5. Press button to select twinning staging logic
choice; press Next button.
6. Press button to select staging logic choice; press
Next button.
7. Press UP/DOWN buttons to select lead-lag change
over time; press Next button.
8. Press button to select continuous blower logic
choice; press Next button.
9. Press button to select degrees choice (Fahrenheit/
Celsius); press Next button.
10. Press button to select temperature sensor logic
choice; press Next button.
11. Press button to select REM 1 temperature sensor
choice; press Next button.
12. Press button to select REM 2 temperature sensor
choice; press Next button.
13. Press UP/DOWN buttons to select equipment
minimum run time; press Next button.
14. Press UP/DOWN buttons to select maximum
number of units while in generator mode; press
Next button.
15. Press UP/DOWN buttons to select touch screen
display brightness; press Next or Home button.
Date/Time Setup Menu
1. Press Setup button on Home screen.
2. Press Date/Time Setup button.
3. Press UP/DOWN arrow to select Hour.
4. Press UP/DOWN arrow to select Minute.
5. Press UP/DOWN arrow to select AM/PM.
6. Press Next button.
7. Press UP/DOWN arrow to select Month.
8. Press UP/DOWN arrow to select Day.
9. Press UP/DOWN arrow to select Year.
10. Press Next button.
11. Press Home button.

Table of Contents