MNL-126509
April 4, 2013 Page 61
Figure 4-4 Correction Factor for Cartridge Operating Hours
Figure 4-5 Example Record of Adjusted Operating Hours
°F
[°C x 9/5 +32]
°C
[
(°F - 32) x 5/9]
Correction Factor
50 122 0.21
40
104 0.34
30 86
0.58
20 68 1.00
10
50 1.81
0
32
3.44
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
0 °C
10 °C 20 °C 30 °C 40 °C 50 °C
Conversion Factor
32 °F 50 °F 68 °F 86 °F 104 °F 122 °F
Date
Operating
Hours
Ambient Temp.
during Compression +18 °F
Correction
Factor
Adjusted Cartridge Hours
Today Total
10/19/04 8 92°F
(33 °C)
0.5 16.00 16.00
11/01/04 4 45°F
(7.2 °C)
2.25 1.78 17.78
Op hrs
Corr. factor
Total hrs
+Today hrs